The table below is a guide to sizing the correct cable gland for a given cable. Individual applications may require different glands, please confirm with cable supplier.

To suit PVC/SWA/PVC & XLPE/SWA/PVC 600/1000 Volt Power Cables

CABLE SPEC

GLANDS

Conductor Area mm² Number of cores BW indoor glands CW outdoor glands
1.5 2 20 20
3 20 20
4 20 20
2.5 2 20 20
3 20 20
4 20 20
4 2 20 20
3 20 20
4 20 20
6 2 20 20
3 20 20
4 25 25
10 2 25 25
3 25 25
4 25 25
16 2 25 25
3 25 25
4 25 25
25 2 25 25
3 32* 32*
4 32 32
35 2 32 32
3 32 32
4 32 32

* Note: 25mm glands are suitable for most 3-core 25mm² cables depending upon the diameter of the cable beneath the armour. Please confirm with cable supplier

CABLE SPEC

GLANDS

Conductor Area mm² Number of cores BW indoor glands CW outdoor glandsLM Tubes
1.5 2 20 20 x
3 20 20 x
4 20 20 x
2.5 2 20 20 x
3 20 20 x
4 20 20 x
4 2 20 20 x
3 20 20 x
4 20 20 x
6 2 20 20 x
3 20 20 x
4 25 25 x
10 2 25 25 x
3 25 25 x
4 25 25 x
16 2 25 25 x
3 25 25 x
4 25 25 x
25 2 25 25 x
3 32* 32* x
4 32 32 x
35 2 32 32 x
3 32 32 x
4 32 32 x